Magnetic Level Indicators

Ex Proof Standard Transmitter

The transmitter must be connected with a certified energy limiting device (e.g. Zener barrier) installed in a safe area. This device guarantees the electrical limit values specified below, including the cable. The metal housing of the transmitter must be connected to protection ground.


Approvals, Ex Proof Standard Transmitter

ATEX ZELM Ex, Type Examination Certificate  |  CE Declaration of conformity  |  Gost-R  |  Gost-R Ex  |  IECEx Certificate of Conformity  |  RTN  |  Föderales staatl. Amt für Gesundheitswesen der Stadt Moskau


Type 32607-NI

Loop supply voltage14 to 30VDC
Signal output4 to 20mA
Media temperature -50 to +150°C
Ambient temperature-20 to +50°C
Enclosure IP68
Housingstainless steel 316 / 316L
Cable gland PA, blue
Seal Perbunan (NBR)
Cable PVC, blue
Output loadmax. 100 Ω at 14 VDC
max. 900 Ω at 30 VDC
Protection type II 2 GD T135°C Ex ia IIC T4
ApprovalZELM 03 ATEX 0168

Type 32608-ND

Loop supply voltage14 to 30VDC
Signal output4 to 20mA
Media temperature -50 to +150°C
Ambient temperature-20 to +50°C
Enclosure IP68
Housingstainless steel 316 / 316L
Cable gland PA, blue
Seal Perbunan (NBR)
Cable PVC, blue
Output loadmax. 100 Ω at 14 VDC
max. 900 Ω at 30 VDC
Protection type II 2 GD T85°C, Ex d IIC T6
ApprovalZELM 03 ATEX 0191X